Neutral Sizing with Harmonics

4-core cable size when third harmonics load the neutral

Design data
A
%
Settings & basis
ResultPreliminary · verify before design
Cable size (4-core)95 mm²Cu XLPE on perforated tray · sized on the neutral current
ReviewNeutral current 158 A is higher than the phase current: the neutral governs the cable size
Neutral current (3 × h3 × Ib)158 A
Sized onNeutral current
Harmonic reduction factor (Table E.52.1)0.86
Combined derating Ca × Cg0.713
Required tabulated rating257 A
Tabulated rating of selection298 A

Table E.52.1: h3 ≤ 15 % size on phase current (f 1.0); 15–33 % phase current, f 0.86; 33–45 % neutral current, f 0.86; above 45 % neutral current, f 1.0. Ratings: IEC 60364-5-52 Method E, Cu XLPE multicore. Check voltage drop and the protective device separately.

What to verify before design ↓

Verify before using in design

  • Get the harmonic content from measurements or the equipment data (LED drivers, IT loads, UPS and VFD inputs are typical sources).
  • Check voltage drop, short-circuit withstand and the protective device; a neutral carrying more than the phase current is not protected by the phase overcurrent devices alone.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Nov 2026✓ Tested against worked examples

Formula

IN = 3 · h3 · Ib It = I(basis) ÷ f ÷ (Ca · Cg) f per IEC 60364-5-52 Table E.52.1

Standards and references

  • IEC 60364-5-52:2009, Annex E, Table E.52.1
  • BS 7671:2018+A3:2024, Appendix 4, Table 4Aa
  • IEC 60364-5-52:2009, reference method E (ratings)

Assumptions

  • Balanced three-phase load; the third harmonic (and its multiples) add in the neutral, so IN = 3 × h3 × Ib.
  • 4-core or 5-core cable with the neutral the same size as the phases, copper XLPE on perforated tray in air.

Inputs and units

Phase design currentA
Third harmonic in phase current%0–60
Ambient temperature—
Circuits grouped on tray—

Typical range: last column

Worked example (default values)

  • Phase design current150 A
  • Third harmonic in phase current35 %
  • Ambient temperature45 °C
  • Circuits grouped on tray3 circuits
Cable size (4-core)95 mm²Neutral current 158 A is higher than the phase current: the neutral governs the cable size

Next steps

More Electrical calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.