Cable Sizing

Smallest copper XLPE cable for a design current

Design data
A
Settings & basis
ResultPreliminary · verify before design
Selected size70 mm²4-core Cu XLPE on perforated tray · 160 A device
Within limitIb 150 A ≤ In 160 A ≤ Iz 175 A
Protective device In160 A
Combined derating factor0.713
Required tabulated rating224 A
Tabulated rating of selection246 A
Derated capacity Iz175 A
Spare over In10 %

Tray in air only (IEC 60364-5-52 Method E). Buried cables (Method D) need different tables, ground temperature and soil resistivity factors. Sized so the cable is protected by the device (Ib ≤ In ≤ Iz). For fuses and some devices also check I2 ≤ 1.45 Iz. Check voltage drop and short-circuit withstand separately.

What to verify before design ↓

Verify before using in design

  • Check voltage drop (Voltage Drop calculator) and short-circuit withstand.
  • Buried cables, ducts and heavy harmonic loads need different tables and factors.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

Ib ≤ In ≤ Iz It = In ÷ (Ca · Cg) Iz (table) ≥ It

Standards and references

  • IEC 60364-5-52:2009, reference method E (XLPE, copper, multicore)
  • IEC 60364-4-43 (overload protection, Ib ≤ In ≤ Iz)
  • BS 7671:2018+A3:2024, Appendix 4

Assumptions

  • Copper XLPE multicore cable in free air on perforated tray, 3 loaded conductors. Not valid for buried cables or ducts.
  • Ratings at 30 °C ambient, corrected by the selected temperature factor Ca (IEC 60364-5-52 Table B.52.14) and grouping factor Cg (Tables B.52.17 and B.52.20 for cables on trays).
  • The cable is sized on the protective device rating In, so that Ib ≤ In ≤ Iz (IEC 60364-4-43).

Inputs and units

Design currentA1–600
Ambient temperature—
Circuits grouped on tray—
Protective device rating In—

Typical range: last column

Worked example (default values)

  • Design current150 A
  • Ambient temperature45 °C
  • Circuits grouped on tray3 circuits
  • Protective device rating InAuto: next standard ≥ Ib
Selected size70 mm²Ib 150 A ≤ In 160 A ≤ Iz 175 A

Next steps