Insulation Resistance Check

Test voltage, minimum IR and polarisation index

Design data
MΩ
MΩ
MΩ
Settings & basis
ResultPreliminary · verify before design
Minimum insulation resistance≥ 1 MΩTest at 500 V DC
Within limit150 MΩ passes
Test voltage500 V DC
Polarisation index (IR10 ÷ IR1)Enter 1 and 10 min readings

Disconnect or protect sensitive equipment (surge devices, electronics) before testing. New installations normally read far above the minimum; a low but passing value often points to moisture or damage. PI ≥ 2.0 is a common acceptance for motor and transformer windings (IEEE 43); follow your specification.

What to verify before design ↓

Verify before using in design

  • Follow the specification's own minimums where they are higher; MV equipment uses the maker's and the specification's values.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

Minimum IR per IEC 60364-6 Table 6A PI = IR(10 min) ÷ IR(1 min)

Standards and references

  • IEC 60364-6:2016 Table 6A (minimum insulation resistance)
  • BS 7671:2018+A3:2024 Table 64
  • IEEE 43-2013 (polarisation index for rotating machines)

Assumptions

  • Minimum values for low-voltage installations: SELV/PELV 0.5 MΩ at 250 V DC; up to 500 V 1 MΩ at 500 V DC; above 500 V 1 MΩ at 1000 V DC.

Inputs and units

Circuit—
Measured IR (lowest reading)MΩ0.01–100000
IR at 1 min (for PI, optional)MΩ
IR at 10 min (for PI, optional)MΩ

Typical range: last column

Worked example (default values)

  • CircuitUp to 500 V (e.g. 230/400 V)
  • Measured IR (lowest reading)150 MΩ
  • IR at 1 min (for PI, optional)0 MΩ
  • IR at 10 min (for PI, optional)0 MΩ
Minimum insulation resistance≥ 1 MΩ150 MΩ passes