Motor Current

Full-load and starting current

Design data
kW
V
Settings & basis
ResultPreliminary · verify before design
Full-load current66.8 A39.8 kW input
DOL start (≈ 6 × FLC)401 A
Star-delta start (≈ 2 × FLC)134 A
Soft starter (≈ 3 × FLC)200 A
VFD (≈ 1.1 × FLC)73 A

Starting multipliers are typical. Use nameplate and starter data for final selection.

What to verify before design ↓

Verify before using in design

  • Use nameplate current and the starter maker's data.
  • Check cable voltage drop during starting.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

I = P ÷ (√3 · V · cos φ · η) (3-ph) I = P ÷ (V · cos φ · η) (1-ph)

Standards and references

  • IEC 60034-1 (rotating machines)
  • IEC 60034-30-1 (efficiency classes)

Assumptions

  • Three-phase or single-phase motor at full load with the given efficiency and power factor.
  • Starting multipliers are typical values, not guarantees.

Inputs and units

Motor outputkW
System—
VoltageV200–11000
Power factor0.6–0.95
Efficiency0.7–0.98

Typical range: last column

Worked example (default values)

  • Motor output37 kW
  • System3-phase
  • Voltage400 V
  • Power factor0.86
  • Efficiency0.93
Full-load current66.8 A