Generator Sizing

Standby generator kVA from connected load

Design data
kW
%
ResultPreliminary · verify before design
Recommended generator1000 kVAPrime rating, next standard size
Maximum demand640 kW
Demand in kVA800 kVA
Required with loading margin1,000 kVA
Loading at selected size80 %

Check large motor starting and non-linear loads with the manufacturer's sizing tool.

What to verify before design ↓

Verify before using in design

  • Derate for site temperature (often 50 °C in the Gulf) and altitude.
  • Check largest motor starting kVA, step loads and non-linear loads with the maker's tool.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Reviewed by an electrical engineer · Nov 2026

Formula

kVA = (P · DF) ÷ cos φ ÷ loading limit

Standards and references

  • ISO 8528-1:2018 (ratings: prime, standby, continuous)

Assumptions

  • Generator rated at 0.8 PF; demand factor applied to connected load.

Inputs and units

Connected loadkW
Demand factor0.4–1
Generator PF0.7–1
Max loading%60–90

Typical range: last column

Worked example (default values)

  • Connected load800 kW
  • Demand factor0.8
  • Generator PF0.8
  • Max loading80 %
Recommended generator1000 kVA

Next steps

More Electrical calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.