Transformer Sizing

kVA rating from connected load

Design data
kW
%
%
ResultPreliminary · verify before design
Recommended transformer1600 kVANext standard rating
Maximum demand840 kW
Demand in kVA933 kVA
Required with spare and loading limit1,400 kVA
Loading at selected size58 %

Check utility standard sizes and N+1 needs. Many utilities limit distribution transformers to 1600 or 2000 kVA.

What to verify before design ↓

Verify before using in design

  • Derate for ambient temperature and harmonics (K-factor).
  • Confirm utility size limits and N+1 redundancy needs.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Reviewed by an electrical engineer · Nov 2026

Formula

kVA = P × DF ÷ cos φ × (1 + spare) ÷ loading limit

Standards and references

  • IEC 60076-1:2011
  • Utility standard sizes

Assumptions

  • Diversity and spare capacity applied to the connected load.

Inputs and units

Connected loadkW
Diversity factor0.4–1
Power factor0.7–1
Spare capacity%
Max loading%60–90

Typical range: last column

Worked example (default values)

  • Connected load1200 kW
  • Diversity factor0.7
  • Power factor0.9
  • Spare capacity20 %
  • Max loading80 %
Recommended transformer1600 kVA

Next steps