Earth Rod Resistance

Single rod resistance and rods needed

Design data
Ω·m
m
mm
Ω
m
ResultPreliminary · verify before design
Single rod resistance33.5 Ω3.0 m × Ø16 mm rod
Review9 rods in a line needed for 5 Ω
Rods required9
Combined resistance at this spacing4.79 Ω
BS 7430 factor λ (9 rods in a straight line)3.61
Same rods at spacing = rod length5.85 Ω
Same rods at spacing = 2 × rod length4.79 Ω
Recommended spacing≥ 3.0 m (ideally 2 × L)

Rods in a straight line, uniform soil. λ is the BS 7430 factor for rods in a straight line (2 rods 1.00 … 10 rods 3.81); rods in a hollow square use larger factors. Verify by fall-of-potential test (BS 7430).

What to verify before design ↓

Verify before using in design

  • Measure soil resistivity (Wenner test) and allow for dry-season values.
  • Prove the installed value by fall-of-potential test; meet the utility / specification target.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.1 · Nov 2026Basis last checked: Nov 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

R1 = ρ ÷ (2πL) · [ln(8L ÷ d) − 1] Rn = R1 · (1 + λα) ÷ n, α = ρ ÷ (2π R1 s)

Standards and references

  • BS 7430:2011+A1:2015 (earthing)
  • IEEE 80-2013 (substation grounding)

Assumptions

  • Uniform soil resistivity; single vertical rod (Dwight formula).
  • Parallel rods in a straight line, BS 7430 method: Rn = R1 · (1 + λα) ÷ n with α = ρ ÷ (2π R1 s), and λ from the BS 7430 factors for rods in a straight line (2 rods 1.00, 3 rods 1.66, 4 rods 2.15, 5 rods 2.54, 6 rods 2.87, 7 rods 3.15, 8 rods 3.39, 9 rods 3.61, 10 rods 3.81).

Inputs and units

Soil resistivityΩ·m10–3000
Rod lengthm1–6
Rod diametermm
Target resistanceΩ
Rod spacing (in a line)m1–30

Typical range: last column

Worked example (default values)

  • Soil resistivity100 Ω·m
  • Rod length3 m
  • Rod diameter16 mm
  • Target resistance5 Ω
  • Rod spacing (in a line)6 m
Single rod resistance33.5 Ω9 rods in a line needed for 5 Ω

Next steps

More Electrical calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.