Conduit Fill

Cables per conduit size

Design data
mm
mm
ResultPreliminary · verify before design
Conduit fill16.9 %Limit 40 % for 3 or more cables
Within limitWithin the fill limit
Max cables of this size14
Conduit area491 mm²

BS 7671 users may apply the cable factor method instead.

What to verify before design ↓

Verify before using in design

  • Long runs and bends need lower fill; check the project specification.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

Fill = n × d² ÷ D² limits 53 % / 31 % / 40 % (NEC Chapter 9)

Standards and references

  • NFPA 70 (NEC) 2023, Chapter 9 Table 1
  • IET On-Site Guide cable factor method (BS 7671 users)

Assumptions

  • Round cables of one size.

Inputs and units

Conduit internal diametermm
Cable outer diametermm
Number of cables

Typical range: last column

Worked example (default values)

  • Conduit internal diameter25 mm
  • Cable outer diameter4.2 mm
  • Number of cables6
Conduit fill16.9 %Within the fill limit

Next steps