Cable Tray Fill

Percentage fill of a cable tray

Design data
mm
mm
mm
Settings & basis
ResultPreliminary · verify before design
Tray fill27.4 %10 cables of Ø28 mm
Within limitWithin the selected 40 % limit
Cable cross-section total6,158 mm²
Tray usable area22,500 mm²
Max cables at this limit14

Check the project specification: many require spare capacity (e.g. 20–25 %) and single-layer laying for power cables.

What to verify before design ↓

Verify before using in design

  • Many specifications require single-layer power cables and 20–25 % spare.
  • Apply grouping derating to the cable sizes.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.1 · Nov 2026Basis last checked: Nov 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

Fill = Σ(π d² ÷ 4) ÷ (W × H)

Standards and references

  • Project specification and tray manufacturer (fill by area)
  • NFPA 70 (NEC) 392.22: separate rules by tray type and cable size, not checked here

Assumptions

  • Round cables; fill by cross-sectional area against the limit you choose. This is a space check only, not a code compliance check.

Inputs and units

Tray widthmm
Usable depthmm
Cable outer diametermm
Number of cables
Fill limit—

Typical range: last column

Worked example (default values)

  • Tray width300 mm
  • Usable depth75 mm
  • Cable outer diameter28 mm
  • Number of cables10
  • Fill limit40 %
Tray fill27.4 %Within the selected 40 % limit

Next steps

More Electrical calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.