Balancing Valve Flow (Kv)

Water flow from Kv and measured ΔP, vs design

Design data
m³/h
kPa
L/s
Settings & basis
ResultPreliminary · verify before design
Measured flow2.35 L/s8.44 m³/h · 97.7 % of design
Within limitWithin -5 % / +10 % of design
ΔP needed for design flow at this Kv23.0 kPa
Design flow8.64 m³/h
Difference from design-0.05 L/s

Water at about 1,000 kg/m³. Read Kv for the actual handwheel setting from the manufacturer's chart, or use a calibrated balancing instrument that reads flow directly. Balance only after flushing, with strainers clean and all valves open.

What to verify before design ↓

Verify before using in design

  • Use the manufacturer's Kv for the actual setting; measuring-station accuracy is lower at small ΔP.
  • Balance with the proportional method so the index circuit keeps the minimum ΔP.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

Q (m³/h) = Kv × √(ΔP ÷ 100 kPa) ΔP = 100 × (Q ÷ Kv)²

Standards and references

  • CIBSE Commissioning Code W (water distribution systems)
  • BSRIA BG 2 (commissioning water systems)
  • IEC 60534-1 (Kv definition)

Assumptions

  • Kv = flow in m³/h of water at 1 bar (100 kPa) pressure drop across the valve.
  • Water near 1,000 kg/m³; glycol mixtures need correction.

Inputs and units

Kv at the valve settingm³/h0.5–500
Measured ΔP across the valvekPa3–100
Design flowL/s0.05–100
Tolerance—

Typical range: last column

Worked example (default values)

  • Kv at the valve setting18 m³/h
  • Measured ΔP across the valve22 kPa
  • Design flow2.4 L/s
  • Tolerance−5 % / +10 %
Measured flow2.35 L/sWithin -5 % / +10 % of design