Internal Heat Gain

People, lighting and equipment loads

Design data
W
m²
W/m²
W
ResultPreliminary · verify before design
Internal heat gain6.05 kW1.72 TR
People2.60 kW
Lighting1.20 kW
Equipment (diversified)2.25 kW
Per m²40 W/m²

Internal gains only. Add solar, fabric and fresh-air loads for the full cooling load. 130 W/person suits seated office work.

What to verify before design ↓

Verify before using in design

  • Add solar, fabric and fresh-air loads for the full cooling load.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026

Formula

Q = people + lighting + equipment × diversity

Standards and references

  • ASHRAE Handbook — Fundamentals, ch. 18 (internal heat gains)
  • CIBSE Guide A

Assumptions

  • Internal gains only; all lighting heat enters the space.

Inputs and units

Occupants
Heat per personW
Floor aream²
Lighting densityW/m²
Equipment loadW
Equipment diversity0.3–1

Typical range: last column

Worked example (default values)

  • Occupants20
  • Heat per person130 W
  • Floor area150 m²
  • Lighting density8 W/m²
  • Equipment load3000 W
  • Equipment diversity0.75
Internal heat gain6.05 kW