Car Park Ventilation

Extract rates for normal and smoke modes

Design data
m²
m
ACH
ACH
ResultPreliminary · verify before design
Smoke mode extract20.8 m³/s44,143 CFM
Car park volume7,500 m³
Normal mode extract12.5 m³/s
Normal mode26,486 CFM

6 / 10 ACH follows BS 7346-7 practice. Local Civil Defence rules or a CFD study may govern.

What to verify before design ↓

Verify before using in design

  • Local civil defence rules or a CFD study may govern.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026

Formula

Q = V × ACH ÷ 3600

Standards and references

  • BS 7346-7:2013 (car park smoke and heat control)
  • NFPA 88A (parking structures)

Assumptions

  • Enclosed car park, 6 ACH normal and 10 ACH smoke mode by default.

Inputs and units

Car park aream²
Clear heightm2.2–6
Normal modeACH
Smoke modeACH

Typical range: last column

Worked example (default values)

  • Car park area2500 m²
  • Clear height3 m
  • Normal mode6 ACH
  • Smoke mode10 ACH
Smoke mode extract20.8 m³/s

Next steps

More Mechanical & HVAC calculators

Found an error? Tell us