Duct Bank Size & Concrete

Encased duct bank size, concrete, ducts and spacers for a run

Design data
mm
mm
mm
m
mm
m
%
ResultPreliminary · verify before design
Concrete to order27.19 m³25.90 m³ net + 5 % waste for 100 m
Ducts in the bank6 (2 × 3)
Encasement width × height730 × 520 mm
Net concrete per metre0.259 m³/m
Duct length (all ducts, no laps)600 m
Spacer sets68
Minimum trench width at the encasement1,030 mm

Duct sizes, spacing, cover, concrete grade, warning tape and the duct arrangement come from the utility owner's standard drawings (for example the power, telecom or street-lighting authority). Spare ducts, draw ropes and duct plugs are part of most specifications.

What to verify before design ↓

Verify before using in design

  • Duct arrangement, spare ducts, cover and concrete grade against the utility owner's drawing.
  • Separation from other services at crossings and in shared corridors.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Nov 2026✓ Tested against worked examples✓ Reviewed by a senior engineer · Nov 2026

Formula

W = n_c·D + (n_c − 1)·s + 2c H = n_r·D + (n_r − 1)·s + 2c Concrete/m = W·H − n·π·D² ÷ 4

Standards and references

  • Utility owner's standard drawings for duct banks (power, telecom, street lighting)
  • IEC 61386-24 (conduit systems buried underground)
  • Project specification (concrete, cover, warning tape)

Assumptions

  • Rectangular encasement around a regular grid of ducts of one size; spacers at a fixed interval.

Inputs and units

Rows of ducts (layers)1–6
Ducts per row1–8
Duct outside diametermm50–200
Clear spacing between ductsmm25–100
Concrete cover to the outer ductsmm50–150
Route lengthm1–2000
Working space each side of the encasementmm0–600
Spacer interval along the routem0.5–3
Concrete waste allowance%0–15

Typical range: last column

Worked example (default values)

  • Rows of ducts (layers)2
  • Ducts per row3
  • Duct outside diameter160 mm
  • Clear spacing between ducts50 mm
  • Concrete cover to the outer ducts75 mm
  • Route length100 m
  • Working space each side of the encasement150 mm
  • Spacer interval along the route1.5 m
  • Concrete waste allowance5 %
Concrete to order27.19 m³