Sprinkler Demand & Water Storage

Density/area demand, flow and pressure per head, hose allowance and tank volume (NFPA 13)

Design data
m²
Settings & basis
ResultPreliminary · verify before design
Total water demand (sprinklers + hose)2,082 L/min8.1 mm/min over 139 m² + 946 L/min hose allowance
Within limitStorage for 60 minutes: about 125 m³
Flow at the most remote sprinkler98 L/min
Pressure needed at that sprinkler1.49 bar
Sprinklers in the design area (approx.)12
Sprinkler demand (density × area)1,136 L/min
Hose allowance946 L/min
Water storage at the minimum duration125 m³

Preliminary density/area method (NFPA 13 baseline points; durations shown are the lower end: Ordinary 60–90 min, Extra 90–120 min). The hydraulic calculation adds pipe losses and flow imbalance, so the real demand is higher. Local civil defence rules can set other densities, durations and storage: they govern.

What to verify before design ↓

Verify before using in design

  • Confirm the hazard classification and storage heights with the fire engineer.
  • Use the civil defence requirements for densities, durations and tank volumes where they differ.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

Q head = density × area per head P = (Q ÷ K)² Demand = density × design area + hose Storage = demand × duration

Standards and references

  • NFPA 13 (installation of sprinkler systems)
  • Local civil defence code (e.g. Saudi SBC 801, UAE Fire and Life Safety Code, Qatar Civil Defence requirements)
  • Sprinkler maker's listing (K-factor, coverage)

Assumptions

  • Density/area baseline points for standard spray sprinklers; lower-end durations.
  • No pipe losses or flow imbalance; hydraulic calculation needed for design.

Inputs and units

Occupancy hazard—
Area covered by each sprinklerm²6–21
Sprinkler K-factor (metric)—

Typical range: last column

Worked example (default values)

  • Occupancy hazardOrdinary hazard group 2 (0.20 gpm/ft², 1,500 ft²)
  • Area covered by each sprinkler12 m²
  • Sprinkler K-factor (metric)K80 (K5.6 US)
Total water demand (sprinklers + hose)2,082 L/minStorage for 60 minutes: about 125 m³