Fire Pump Selection Check

Rated size, NFPA 20 curve limits and approximate power

Design data
L/min
bar
bar
%
ResultPreliminary · verify before design
Rated pump capacity750 gpm (2,839 L/min)Net rated pressure about 6.5 bar
Within limitDemand is 73 % of the rated flow
Demand flow550 gpm
Maximum churn (shut-off) net pressure, 140 %9.1 bar
Minimum net pressure at 150 % flow, 65 %4.2 bar
Approximate hydraulic power at rated point43.9 kW
Jockey pump start (typical, above main pump start)about 0.3–0.7 bar

NFPA 20 requires a listed pump whose curve stays within 140 % of rated pressure at churn and gives at least 65 % at 150 % flow. Size the driver from the maker's full curve (up to 150 % flow), not the rated point alone. Jockey pump settings follow the controller sequence agreed with the authority.

What to verify before design ↓

Verify before using in design

  • Select a listed pump from the maker's curves and check the whole curve against the demand.
  • Check the driver (electric or diesel) and power supply arrangements with the authority.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

Rated flow = next standard size ≥ demand Net pressure = discharge − suction Power ≈ Q × ΔP ÷ η

Standards and references

  • NFPA 20 (stationary fire pumps)
  • NFPA 25 (inspection, testing and maintenance)
  • Local civil defence requirements

Assumptions

  • Pump rated at the next standard size at or above the demand.
  • Constant suction pressure; power at the rated point only.

Inputs and units

System demand flowL/min
Pressure needed at the pump dischargebar1–25
Suction pressure at the pumpbar
Pump efficiency%40–90

Typical range: last column

Worked example (default values)

  • System demand flow2082 L/min
  • Pressure needed at the pump discharge7 bar
  • Suction pressure at the pump0.5 bar
  • Pump efficiency70 %
Rated pump capacity750 gpm (2,839 L/min)Demand is 73 % of the rated flow

Next steps

More Fire protection calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.