Clean Agent Quantity

Total flooding agent mass for a room (NFPA 2001 method)

Design data
m³
°C
%
Settings & basis
ResultPreliminary · verify before design
Agent quantity82.0 kg0.547 kg per m³ at 7.0 %
Within limitConcentration is below the agent's no-adverse-effect level for occupied rooms
Specific vapour volume S0.1377 m³/kg
Flooding factor0.547 kg/m³
No-adverse-effect level (NOAEL)9.0 %

NFPA 2001 total flooding with constants for the selected agent. Use the design concentration from the system's listed design manual (for HFC-227ea commonly about 6.6–7 % for Class A, higher for Class B); add the maker's allowances for altitude and room openings. The room must pass a door fan integrity test to hold the concentration.

What to verify before design ↓

Verify before using in design

  • Use the design concentration from the listing for the actual hazard (Class A, B or C).
  • Room integrity (door fan) test before handover; check hold time.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

W = (V ÷ S) × C ÷ (100 − C) S = k1 + k2 × T

Standards and references

  • NFPA 2001 (clean agent fire extinguishing systems)
  • ISO 14520
  • System maker's listed design manual

Assumptions

  • Total flooding of a closed room at the minimum expected temperature.
  • No altitude correction or leakage allowance.

Inputs and units

Agent—
Protected volume (net)m³5–5000
Minimum room temperature°C0–40
Design concentration (from the system listing)%4–12

Typical range: last column

Worked example (default values)

  • AgentHFC-227ea (e.g. FM-200)
  • Protected volume (net)150 m³
  • Minimum room temperature21 °C
  • Design concentration (from the system listing)7 %
Agent quantity82.0 kgConcentration is below the agent's no-adverse-effect level for occupied rooms