Pt100 / Pt1000 RTD

Temperature ↔ resistance to IEC 60751, with tolerance class

Design data
°C
Ω
Settings & basis
ResultPreliminary · verify before design
Resistance138.51 ΩPt100 at 100.0 °C
Within limitInside the IEC 60751 range (−200 to 850 °C)
Tolerance (class A)±0.35 °C ≈ ±0.133 Ω
Sensitivity at this temperature0.379 Ω/°C
Resistance at 0 °C (R0)100 Ω

IEC 60751 Callendar–Van Dusen curve for industrial platinum sensors (α = 0.00385). Each tolerance class is valid only over a temperature range that depends on the sensor type (wire-wound or film): check the datasheet. With 2-wire connection the lead resistance adds to the reading; 3- or 4-wire connection removes most of it.

What to verify before design ↓

Verify before using in design

  • Check the class validity range for the sensor type (wire-wound or thin film).
  • On 2-wire sensors, subtract the lead resistance or use 3- or 4-wire connection.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

R = R0 (1 + A t + B t²) for t ≥ 0 R = R0 (1 + A t + B t² + C (t − 100) t³) for t < 0 A = 3.9083×10⁻³, B = −5.775×10⁻⁷, C = −4.183×10⁻¹²

Standards and references

  • IEC 60751:2022 (industrial platinum resistance thermometers)
  • Sensor datasheet (class validity range, connection)

Assumptions

  • Standard platinum curve, α = 0.00385.
  • Lead resistance not included.

Inputs and units

Convert—
Sensor—
Temperature (for temperature → resistance)°C-200–850
Measured resistance (for resistance → temperature)Ω15–4000
Tolerance class—

Typical range: last column

Worked example (default values)

  • ConvertTemperature → resistance
  • SensorPt100
  • Temperature (for temperature → resistance)100 °C
  • Measured resistance (for resistance → temperature)119.4 Ω
  • Tolerance classClass A
Resistance138.51 ΩInside the IEC 60751 range (−200 to 850 °C)

Next steps

More Controls & automation calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.