Mullion Deflection Check

Wind deflection of a simply supported mullion against AAMA or project limits

Design data
mm
mm
kPa
cm⁴
Settings & basis
ResultPreliminary · verify before design
Mid-span deflection17.6 mmAllowed 20.6 mm
Within limitWithin the limit (85 % of it)
Line load on the mullion2.25 kN/m
Required Ixx for this limit342 cm⁴
Deflection as span ratioL/205

Simply supported span with uniform wind load; deflection only. Bending stress, connections, anchors, glass deflection and split or continuous mullions need the façade engineer's full check. Take the design wind pressure from the project wind study or code (ASCE 7, EN 1991-1-4), including higher pressures near corners and the roof.

What to verify before design ↓

Verify before using in design

  • Full structural check by the façade engineer: stress, connections, anchors, split mullions.
  • Wind pressures from the wind study, including corner zones.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

δ = 5 w L⁴ ÷ (384 E I) w = wind pressure × tributary width

Standards and references

  • AAMA TIR-A11 (deflection limits for framing members)
  • ASCE 7 / EN 1991-1-4 (wind loads)
  • Eurocode 9 / Aluminum Design Manual (aluminium members)
  • CWCT Standard for systemised building envelopes

Assumptions

  • Simply supported span, uniformly distributed wind load.
  • Ixx from the supplier's section properties; no composite action with glass.

Inputs and units

Mullion span between supportsmm500–8000
Tributary width (mullion spacing)mm
Design wind pressurekPa0.3–6
Material—
Moment of inertia of the mullion (Ixx)cm⁴5–5000
Deflection limit—

Typical range: last column

Worked example (default values)

  • Mullion span between supports3600 mm
  • Tributary width (mullion spacing)1500 mm
  • Design wind pressure1.5 kPa
  • MaterialAluminium (E = 70,000 MPa)
  • Moment of inertia of the mullion (Ixx)400 cm⁴
  • Deflection limitAAMA TIR-A11: L/175 up to 4.1 m, then L/240 + 6.35 mm
Mid-span deflection17.6 mmWithin the limit (85 % of it)

Next steps

More Façade calculators

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.