Glazing Heat Gain

Peak solar and conduction gain through glass, in kW and TR

Design data
m²
W/m²
W/m²K
°C
°C
ResultPreliminary · verify before design
Peak heat gain through the glazing21.5 kWAbout 6.1 TR of cooling
Within limitSolar gain is 82 % of the glazing load: shading and SHGC matter most
Solar gain (A × SHGC × irradiance)17.5 kW
Conduction (U × A × ΔT)4.0 kW
Gain per m² of glass215 W/m²

A simplified peak check for comparing glass and shading options, not a cooling load calculation. Irradiance depends on orientation, time of day and season: east and west façades in the Gulf see the highest peaks. Take SHGC and U-value for the whole glazing unit from the maker's data (NFRC or EN 410 / EN 673); frames and external shading change both.

What to verify before design ↓

Verify before using in design

  • Use the HVAC engineer's load calculation or energy model for design.
  • Check glass data sheets match the approved sample (coating position, interlayer).
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

Q = A × SHGC × I + U × A × (T outdoor − T indoor) 1 TR = 3.517 kW

Standards and references

  • ASHRAE Handbook: Fundamentals (fenestration heat gain)
  • NFRC 200 / EN 410 (solar heat gain, g-value)
  • NFRC 100 / EN 673 (U-value)
  • Energy code or rating system limits (e.g. ASHRAE 90.1, GSAS, Mostadam)

Assumptions

  • Peak instantaneous gain; no thermal storage or time lag.
  • SHGC and U-value for the whole unit; no external shading unless included in SHGC.

Inputs and units

Glazed aream²
Solar heat gain coefficient (SHGC / g-value)0.1–0.9
Peak solar irradiance on the façadeW/m²100–1100
Glazing U-valueW/m²K0.5–6
Outdoor design temperature°C
Indoor design temperature°C

Typical range: last column

Worked example (default values)

  • Glazed area100 m²
  • Solar heat gain coefficient (SHGC / g-value)0.25
  • Peak solar irradiance on the façade700 W/m²
  • Glazing U-value1.8 W/m²K
  • Outdoor design temperature46 °C
  • Indoor design temperature24 °C
Peak heat gain through the glazing21.5 kWSolar gain is 82 % of the glazing load: shading and SHGC matter most