Drainage Pipe Capacity

Full-bore flow by Manning's equation

Design data
mm
%
Settings & basis
ResultPreliminary · verify before design
Full-bore capacity19.8 L/sat 1 % gradient
Within limitSelf-cleansing velocity achieved
Full-bore velocity1.12 m/s
Gradient as ratio1 : 100
Flow area176.7 cm²

Design gravity drains to run part-full (typically up to 75 % depth). Check the local drainage authority's rules.

What to verify before design ↓

Verify before using in design

  • Design to run part-full and keep self-cleansing velocity (often ≥ 0.75 m/s).
  • Follow the local drainage authority's rules.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026

Formula

v = (1/n) · R^(2/3) · S^(1/2) Q = v · A

Standards and references

  • Manning equation
  • BS EN 752:2017 / BS EN 12056-2

Assumptions

  • Full-bore uniform flow with the Manning n of the selected material.

Inputs and units

Internal diametermm
Gradient%0.3–10
Pipe material—

Typical range: last column

Worked example (default values)

  • Internal diameter150 mm
  • Gradient1 %
  • Pipe materialuPVC · n 0.010
Full-bore capacity19.8 L/sSelf-cleansing velocity achieved

Next steps

More Plumbing calculators

Found an error? Tell us