Pipe Velocity

Water velocity for a pipe size

Design data
L/s
mm
ResultPreliminary · verify before design
Velocity1.51 m/sin 65 mm bore
Within limitWithin 0.6–2.5 m/s water range
Flow area33.18 cm²
Flow18.00 m³/h
Flow79.3 US gpm
What to verify before design ↓

Verify before using in design

  • Keep velocities roughly 0.6–2.5 m/s in water supply to limit noise and erosion.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026

Formula

v = Q ÷ A A = πD² ÷ 4

Standards and references

  • Continuity equation
  • BS EN 806-3 / CIBSE Guide G (recommended velocities)

Assumptions

  • Full pipe flow; internal diameter entered.

Inputs and units

FlowL/s
Internal diametermm10–1000

Typical range: last column

Worked example (default values)

  • Flow5 L/s
  • Internal diameter65 mm
Velocity1.51 m/sWithin 0.6–2.5 m/s water range

Next steps

More Plumbing calculators