Gulf cities are full of buried power cables, fibre, water and gas lines, and records are often incomplete. Striking a live cable or a main is one of the most dangerous and expensive mistakes on site.

Before excavation

  • Collect utility records from every owner and the authority's NOC (no-objection) process.
  • Scan the area with a cable avoidance tool (CAT and signal generator) and, where needed, ground-penetrating radar (GPR).
  • Mark detected services on the ground with the agreed colour code and record them on a drawing.
  • Utility surveys are often classified by quality levels (for example PAS 128 in the UK): records only, detection, verified by trial holes.

Trial holes and safe digging

  • Confirm critical services with hand-dug or vacuum-excavated trial pits before machine digging.
  • Keep machines away from marked services by the distance in the permit; dig by hand near them.
  • Treat every cable as live until proven otherwise; stop and report any unknown service.

Recording

  • Survey exposed services (position, depth, size, type) before backfilling and add them to the as-built drawings.
  • Share the records with the client and the utility owners; they protect the next contractor.
Good to knowScan again on the morning of the dig. Marks fade, get moved, and other contractors dig nearby overnight.

Use with this guide