Solar PV & Battery

Array size and battery bank for a daily load

Design data
kWh/day
h
%
W
days
Settings & basis
ResultPreliminary · verify before design
PV array size6.82 kWp13 × 550 W panels
Installed capacity7.15 kWp
Battery bank868 Ah at 48 V
Battery energy41.7 kWh
Inverter AC size (installed DC ÷ 1.2, before choosing a standard size)6.0 kW
Approx. yearly energy11,483 kWh/yr
Panel area (≈ 2.6 m² per panel)34 m²
Approx. roof area incl. row spacing (× 1.4)47 m²

Gulf locations typically see 5.5–6.5 peak sun hours. Dust and heat losses are higher than in cooler climates.

What to verify before design ↓

Verify before using in design

  • Use site irradiance data (PVGIS, PVsyst) and module temperature derating.
  • Check inverter sizing and the utility's net-metering rules.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.1 · Nov 2026Basis last checked: Nov 2026✓ Tested against worked examples✓ Reviewed by an electrical engineer · Nov 2026

Formula

kWp = E ÷ (PSH × (1 − losses)) Ah = E × days ÷ (V × DoD × η)

Standards and references

  • IEC 62548-1:2023 (PV array design)
  • IEC 62446-1 (testing)

Assumptions

  • Peak sun hours and system losses entered by you.
  • Battery bank sized for the energy delivered to the load: efficiency of the discharge path (battery + inverter), 90 % by default. This is not the round-trip (charge and discharge) efficiency.
  • Roof area allows about 40 % extra for row spacing and walkways on a flat roof; inverter sized at a DC/AC ratio of about 1.2.

Inputs and units

Daily energy usekWh/day
Peak sun hoursh3–7.5
System losses%10–35
Panel ratingW
Battery autonomydays
Battery voltageV
Depth of discharge0.5–0.95
Battery + inverter efficiency (discharge)0.8–0.97

Typical range: last column

Worked example (default values)

  • Daily energy use30 kWh/day
  • Peak sun hours5.5 h
  • System losses20 %
  • Panel rating550 W
  • Battery autonomy1 days
  • Battery voltage48 V
  • Depth of discharge0.8
  • Battery + inverter efficiency (discharge)0.9
PV array size6.82 kWp

Next steps

Found an error? Tell us

Describe the problem briefly (the wrong value, the right one, and the reference if you have it). The page name is sent automatically.