Construction Noise at a Receiver

Combine sources, attenuate with distance and compare with the limit

Design data
dB(A)
dB(A)
dB(A)
dB(A)
m
m
dB(A)
ResultPreliminary · verify before design
Level at the receiver70.6 dB(A)84.6 dB(A) combined at 10 m, minus 14.0 dB for distance
Over limitExceeds the limit by 5.6 dB: move or quieten equipment, add a barrier, or limit working hours
Combined level of all sources84.6 dB(A)
Distance needed to meet the limit96 m
Sources counted3

Point sources in free field: each doubling of distance takes off about 6 dB. Ground absorption, barriers, buildings and wind change real levels (ISO 9613-2 gives the full method). Two equal sources add 3 dB, not double. Use measured or manufacturer levels for your equipment and the limits in your environmental permit.

What to verify before design ↓

Verify before using in design

  • Measure at the receiver with a calibrated sound level meter.
  • Check the limits and hours in the environmental permit.
  • Check the edition of each standard that your project specification calls for.
  • Confirm with manufacturer data and the approved design before construction.
Basis & methodVersion 1.0 · Nov 2026Basis last checked: Oct 2026✓ Tested against worked examples

Formula

L total = 10 log₁₀ Σ 10^(Li/10) L receiver = L ref − 20 log₁₀(r2 ÷ r1)

Standards and references

  • ISO 9613-2 (attenuation of sound outdoors)
  • BS 5228-1 (noise control on construction sites)
  • Environmental permit noise conditions

Assumptions

  • Point sources in free field, 6 dB per doubling of distance.
  • No barriers, ground absorption or reflections.

Inputs and units

Source 1 level at the reference distancedB(A)40–130
Source 2 (0 = none)dB(A)
Source 3 (0 = none)dB(A)
Source 4 (0 = none)dB(A)
Reference distance of the levelsm1–100
Distance to the receiverm1–5000
Noise limit at the receiver (permit or project)dB(A)35–90

Typical range: last column

Worked example (default values)

  • Source 1 level at the reference distance80 dB(A)
  • Source 2 (0 = none)82 dB(A)
  • Source 3 (0 = none)75 dB(A)
  • Source 4 (0 = none)0 dB(A)
  • Reference distance of the levels10 m
  • Distance to the receiver50 m
  • Noise limit at the receiver (permit or project)65 dB(A)
Level at the receiver70.6 dB(A)Exceeds the limit by 5.6 dB: move or quieten equipment, add a barrier, or limit working hours